- Configurable top with solid closure panels
- Welded sides with upper/lower vents
- Open front and back (optional door and rear access cover)
- Open base
- Green ground wire (cabinet to interior rack)
- Side supports for optional accessories
- Pilot Point screws with captive washers
- Provisions for anchoring
- Beveled corners
- Black wrinkle powder epoxy finish
- Corner post mounting rails tapped 10-32 with RU increments marked
- Inner platform base with casters and stainless steel ball transfers
- Three lacing panels in cabinet and three in rack
- Load capacity 750 lbs.
- Installation: Allow 3.5 in. minimum clearance on both sides for rotation
- Rack Space: 24U
- Height (Exterior Cabinet): 53.86 in.
- Width (Exterior Cabinet): 24.00 in.
- Depth (Exterior Cabinet): 32.875 in. (26.00 usable)
- Interior rack 50.11 in. high (24U) x 24 in. deep (26 in. useable allows equipment to extend 2 in. beyond rack)
- Maximum rollout 25.00 in. (57.875 in. overall rollout depth)
The two-part host style rack shall be Lowell Model LHR-2432 which shall be made in the U.S.A. with certified U.S. steel and have overall measurements of 53.86″H x 24.00″W x 32.875″D with panel space of 24 rack units and useable depth of 26.00″. It shall be comprised of an external welded steel cabinet and an internal pull-out rack that is connected to an inner platform caster base with stainless steel ball transfers capable of supporting 750 lbs. The external cabinet shall have vented sides, open front, open back, three rear lacing panels, 10U EIA top opening with solid closure panels, and top knockouts for conduit and wireless antennas. It shall have a black wrinkle textured powder epoxy finish, provisions for anchoring, and a ground wire to the internal rack. The internal rack shall be a steel assembly with corner post mounting rails tapped 10-32, three rear lacing panels, and side/rear braces. It shall be mounted to the caster base and pull-out smoothly from the cabinet to provide free rotation to rear connections. The internal rack/caster base assembly shall be capable of disengaging from the external cabinet for shop wiring and testing.